Y(st)Y Dca-s2 1 x 2 x 0,8 mm (H500)
Y(st)Y Dca-s2 1 x 2 x 0,8 mm (H500)
Nexans Y(st)Y Dca-s2 is a signal cable according to fire classification Dca-s2,d2,a3 for usage in low voltage installations with a medium fire hazard level
Read more- Nexans ref. : 10562261
 - EAN : 5413404323715
 
Description
Description
Standards
- 
                                            TestIEC 60332-1
 
Application
Nexans Y(st)Y Dca-s2 is a signal cable according to fire classification Dca-s2,d2,a3 for usage in signal applications in low voltage installations with a medium fire hazard level. The metallised foil protects against interference with external electrical fields.
Description
- Conductor: 0.8 mm solid plain copper, class 1
 - Insulation: PVC
 - Conductors brunched into pairs (except for 1x4x0,8 = 1quad)
Pairs laid up in concentric layers - Plastic sperating foil over cable core
 - Screening: Metallised foil over drain wire
 - Outher sheath: PVC
Colour: Grey or white 
Core Identification
according NEN 1597 (see technical data, table A)
Characteristics
Characteristics
Construction characteristics
Construction characteristics
                                                                Conductor material
                                                            
                                                            
                                                                Plain copper 
                                                            
                                                        
                                                                Sheath colour
                                                            
                                                            
                                                                Grey 
                                                            
                                                        
                                                                Conductor flexibility
                                                            
                                                            
                                                                Solid 
                                                            
                                                        
                                                                Insulation
                                                            
                                                            
                                                                PVC 
                                                            
                                                        
                                                                Outer sheath
                                                            
                                                            
                                                                Fire-retardant PVC 
                                                            
                                                        
                                                                Screen
                                                            
                                                            
                                                                - 
                                                            
                                                        Dimensional characteristics
Dimensional characteristics
                                                                Number of pairs
                                                            
                                                            
                                                                1 
                                                            
                                                        
                                                                Conductor diameter
                                                            
                                                            
                                                                0.8 mm
                                                            
                                                        
                                                                Nominal outer diameter
                                                            
                                                            
                                                                5.9 mm
                                                            
                                                        
                                                                Approximate weight
                                                            
                                                            
                                                                38 kg/km
                                                            
                                                        
                                                                Diameter over insulation
                                                            
                                                            
                                                                - mm
                                                            
                                                        
                                                                Number of cores
                                                            
                                                            
                                                                - 
                                                            
                                                        Electrical characteristics
Electrical characteristics
                                                                Maximal capacity at 800Hz
                                                            
                                                            
                                                                - nF/km
                                                            
                                                        
                                                                Capacitance unbalance pair to pair
                                                            
                                                            
                                                                - pF/km
                                                            
                                                        
                                                                Capacitance unbalance pair to ground
                                                            
                                                            
                                                                - pF/km
                                                            
                                                        
                                                                Ohmical resistance of the insulation
                                                            
                                                            
                                                                1000 MOhm.km
                                                            
                                                        
                                                                Breakdown voltage
                                                            
                                                            
                                                                0.8 kV
                                                            
                                                        
                                                                Maximum operating voltage
                                                            
                                                            
                                                                150 V
                                                            
                                                        
                                                                Max. DC resistance of the conductor at 20°C
                                                            
                                                            
                                                                38.2 Ohm/km
                                                            
                                                        Mechanical characteristics
Mechanical characteristics
                                                                Cable flexibility
                                                            
                                                            
                                                                Rigid 
                                                            
                                                        
                                                                Mechanical resistance to impacts
                                                            
                                                            
                                                                Normal domestic use 
                                                            
                                                        Usage characteristics
Usage characteristics
                                                                Packaging
                                                            
                                                            
                                                                Drum 500 m 
                                                            
                                                        
                                                                Field of application
                                                            
                                                            
                                                                Indoor 
                                                            
                                                        
                                                                Ambient installation temperature, range
                                                            
                                                            
                                                                -5 ... 50 °C
                                                            
                                                        
                                                                Operating temperature, range
                                                            
                                                            
                                                                -15 ... 70 °C
                                                            
                                                        
                                                                Bending factor when laying
                                                            
                                                            
                                                                10 (xD)
                                                            
                                                        
                                                                Resistance to vibrations
                                                            
                                                            
                                                                No 
                                                            
                                                        Resources
Resources
Selling & delivery Information
Marking
NEXANS-NL Y(st)Y Dca NxPxS  mm
N = no. of pairs, P = pair or quad, S = section in mm
Declaration of Performance
- Declaration of Performance n� : 1000937-BEBU
 - Certification Date : 12/1/23
 - AVCP (Assessment and Verification of Constancy of Performance) : System 3
 - Notified body : NB 2659
 - Declared performance : Dca-s2,d2,a3
 
Dealer locator