- Products
- Markets
- Services & Tools
- Newsroom
- CSR
- Blog
- We are Nexans
- Search
- Contact us
- Compare
- Sign in
YMvK ss Dca ULTIMO ULTRAFLEX 0.6/1 kV 5G70 mm2 MTR
Certifications and labels
Environmental data
YMvK ss Dca ULTIMO ULTRAFLEX 0.6/1 kV 5G70 mm2 MTR
Nexans ULTIMO is the new standard in installation cables. With Nexans YMvK ss Dca ULTIMO ULTRAFLEX, you choose maximum flexibility without compromising on capacity or safety. The cable features super flexible Class 5 conductors with the same electrical performance as a standard YMvK conductor. This allows you to use YMvK ss Dca ULTIMO ULTRAFLEX in situations where you would normally apply a standard YMvK, without needing to adjust the cross-section. You pull and lay the cable more easily through tight shafts and winding routes, and connecting it in crowded cabinets and other confined spaces is noticeably simpler. The cable is UV-resistant, meets fire class Dca-s2,d2,a3 according to EN 50575, and comes with an EPD environmental product declaration (PEP EcoPassport).
Read more- Nexans ref. : 10559963
- EAN : 5413404322442
Description
Description
Standards
-
ProductHD 604.4D; IEC 60228; IEC 60502
-
TestKEMA 42 C-1-4-D
Key features of Nexans ULTIMO
- Easy to bend: super flexible Class 5 conductors with DC resistance at Class 2 level, ideal for tight bends and confined spaces.
- Standards-compliant safety: fully suitable for applications designed according to NEN 1010 with standard installation cables; you can continue using the same cross-sections and cable tables.
- UV-resistant: suitable for outdoor use; the cables meet the 720-hour test according to EN 50289-4-17 Method A.
- Equipped with EPD environmental product declaration: PEP EcoPassport gives you insight into the ecological footprint of the cables.
APPLICATION
Nexans YMvK ss Dca ULTIMO ULTRAFLEX is a power cable according to fire classification Dca-s2,d2,a3, for usage in low voltage installations up to 0.6/1 kV in housing, residential and similar installations with a medium fire hazard level. YMvK ss Dca ULTRAFLEX® is suitable for fixed installation in sight, with clamps or saddles. Use of this cable in special trays and ducts is allowed. This cable has a reduced propagation of fire in cable bunches..
Design
- Conductor
Bare copper
Highly flexible, class 2 / 5 (Conductor construction according to IEC 60228 class 5, conductor resistance according to class 2) - Insulation: XLPE
- Inner covering filling compound or filler compound
- Outer sheath: PVC
Colour: grey
UV resistance: Yes
Performance class
Declaration of Performance
Reaction to fire: Dca-s2,d2,a3
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Current capacity table PR three phase multicore NL
| Conductor cross-section |
|
|
|
|
|
|
|---|---|---|---|---|---|---|
| mm² | Cu | Cu | Cu | Cu | Cu | Cu |
| 70.0 | 164.0 | 194.0 | 167.0 | 229.0 | 188.0 | 246.0 |
| A2 Multi-core cable in conduit in a thermally insulated wall |
| B2 Multi-core cable in conduit on a wooden wall |
| D1 Multi-core cable in ducts in the ground |
| C Single-core or multi-core cable on a wooden wall |
| D2 Multi-core cables designed to be buried directly in the ground |
| E Multi-core cable in free air |
Current capacity table PR single phase multicore
| Conductor cross-section |
|
|
|
|
|
|
|---|---|---|---|---|---|---|
| mm² | Cu | Cu | Cu | Cu | Cu | Cu |
| 70.0 | 183.0 | 221.0 | 203.0 | 269.0 | 225.0 | 286.0 |
| A2 Multi-core cable in conduit in a thermally insulated wall |
| B2 Multi-core cable in conduit on a wooden wall |
| C Single-core or multi-core cable on a wooden wall |
| D1 Multi-core cable in ducts in the ground |
| D2 Multi-core cables designed to be buried directly in the ground |
| E Multi-core cable in free air |
Current capacity table PR single phase single core
| Conductor cross-section |
|
|
|
|
|---|---|---|---|---|
| mm² | Cu | Cu | Cu | Cu |
| 70.0 | 200.0 | 253.0 | 269.0 | 310.0 |
| A1 Insulated conductors in conduit in a thermally insulated wall |
| B1 Insulated conductors in conduit on a wooden wall |
| C Single-core or multi-core cable on a wooden wall |
| F Single-core flat cables, touching in free air |
Current capacity table PR three phase single core
| Conductor cross-section |
|
|
|
|
|
|
|
|---|---|---|---|---|---|---|---|
| mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
| 70.0 | 179.0 | 222.0 | 167.0 | 229.0 | 188.0 | 268.0 | 279.0 |
| A1 Insulated conductors in conduit in a thermally insulated wall |
| B1 Insulated conductors in conduit on a wooden wall |
| D1 Single or Multi-core cable in ducts in the ground |
| C Single-core or multi-core cable on a wooden wall |
| D2 Single or Multi-core cables designed to be buried directly in the ground |
| F Single-core trefoil cables, touching in free air |
| F Single-core flat cables, touching in free air |
Selling & delivery Information
Marking
YMvK ss Dca-s2,d2,a3
n (x or G) s mm²
NEXANS ULTIMO
KEMA KEUR
Meter Marking
n = no. of conductors
s = cross section in mm²
x = without green/yellow
G = with green/yellow
Declaration of Performance
- Declaration of Performance n° : 1000904-BEDO
- Certification Date : 12/1/23
- AVCP (Assessment and Verification of Constancy of Performance) : System 3
- Notified body : NB 2659
- Declared performance : Dca-s2,d2,a3
YMvK ss Dca ULTIMO ULTRAFLEX 0.6/1 kV 5G70 mm2 MTR
Nexans ref. : 10559963
EAN : 5413404322442
PEP : NXNS-00203-V01.01