Over Nexans
Produkten & Oplossingen
Klantenservice
Werken bij Nexans
Nieuws - Pers
Applications
For inside and outside use in railway vehicles (locomotives, trains, trolley busses, etc.), switching stations and control panels. Installation in cable ducts, tubes and outside.
For wiring in switching stations and distribution boards up to 1.000 V, this cable is short-circuit and earth fault save.
Current-carrying capacity acc. to EN 50343 as well as VDE 0298 part 4.Serves request with regard to Hazard Level 4 acc. to EN 45545-1
Design
1. Conductor
Flexible stranded tinned copper, acc. to DIN VDE 0295/IEC 60228/HD 383 class 5, conductor wrapping optonal
2. Insulation
High grade silicon type EI112 acc. to EN 50382-1
3. Outer sheath
High grade silicon, type EM107 acc. to EN 50382-1, oil, diesel-oil, ozone and uv resistant
Cable marking
Marking white
RHEYHALON 180 (N)S2HXAFOE 3,6/6 kV (EN) 50382-.2 3600V 1x50 OF
Core colours
yellow (YE)
Addional Standards
DIN 5510 part 1 Flame protection class 1, 2, 3 and 4; BS 6853
Nominal voltage
Uo/U (Umax) = 3.6/6 (7.2) kV
Max. operating voltage in d.c. installations, one-sided earthed
Uo= 6.5 kV DC
Testing a.c. voltage (5 minutes)
U = 12.5 kV
Conductor at normal operation
≤ 150 °C/100.000 h
≤ 180 °C/20.000 h
Conductor under short-circuit conditions (tinned)
≤ 350 °C
Special conditions relating temperature and bending radii (e.g. by compelled guidance into cluthes, wagon transition and boogies) on request.