For inside and outside use in railway vehicles (locomotives, trains, trolley busses, etc.), switching stations and control panels. Installation in cable ducts, tubes and outside.
For wiring in switching stations and distribution boards up to 1.000 V, this cable is short-circuit and earth fault save.
Current carrying capacity acc. to EN 50343 as well as VDE 0298 part 4. Serves request with regard to Hazard Level 4 acc. to EN 45545-1
1. Conductor
Flexible stranded tinned copper, acc. to DIN VDE 0295/IEC 60228/ HD 383 class 5; conductor wrapping optional
2. Insulation
Special cross-linked EPR, rubber type EI110 acc. to EN 50264-1
3. Outer sheath
Special cross-linked EVA, rubber type EM104 acc. to EN 50264-1, oil, diesel-oil, ozone and uv resistant.
Ink-marking white
RHEYHALON VDE-Reg.-Nr. 7906 ; NSHXAFOE EN 3.6/6 kV 9GKW EN 50264-3-1 3600V 2.5 MM ; FA-Nr. ...
Black (BK)
DIN 5510 part 1 Flame protection class 1, 2, 3 and 4 BS 6853
Nominal voltage
Uo/U (Umax) = 3.6/6 (7.2) kV
Max. operating voltage in d.c. installations, one-sided earthed
Uo= 5.4 kV DC
Testing a.c. voltage (5 minutes)
U = 12 kV
Conductor at normal operation
≤ 90 °C/250.000 h
≤ 120 °C/20.000 h
Overload
≤ 160 °C / 50 h
Conductor under short-circuit conditions (tinned)
≤ 200 °C