Nederlands Login Get Registered Catalog Browser Contact Us
Global expert in cables and cabling system

About Nexans

Products and Solutions

Customer Service

Work at Nexans

News and Press

Go

RE-2Y(St)YSWAY - fl LSLH

Send link to this page print Your Nexans contact on this page
RE-2Y(St)YSWAY - fl LSLH - Intrumentation cables 300 V
- Overall screen (OS)
- Low smoke, low halogen (LSLH)
- Oil resistant
Standards
International  IEC 60228; IEC 60332-3-22 Cat.A; IEC 60754; IEC 61034
Description

Applications

These cables are intended for transmission of analogue and digital signals. They allow transmission over long distances at high pulse rates. These cables are used in industrial installations (refineries, chemical plants, etc...) where there is a potential risk of mechanical damage.

 

Design

Conductor:

Stranded bare copper (class 2)

Insulation:

Polyethylene (PE)

Overall screen:

Tinned copper drain wire

Aluminium/polyester tape

Inner sheath:

Polyvinyl chloride (PVC)

Colour: black

Armour:

Galvanized steel wires (SWA)

Outer sheath:

Polyvinyl chloride (PVC)

Special low smoke, low halogen (LSLH)

Colour: black or blue

 

Fire retardant: IEC 60332-3-22(A), limiting oxygen index > 30 as par ASTM D 2863

Low smoke: IEC 61034-2, transmittance > 40 %

Low halogen: IEC 60754-1 HCL < 6 %

 

Core identification

Pair: Black/white
For multipair  White core printed with pair number

 

Marking

GORSE YYYY RE - 2Y(St)YSWAY - fl LSLH 300V Nber of pairs & cross-section IEC 60332-3-22(A) + metric marking

 

Désignation

RE: Instrumentation cable
2Y: Polyethylene insulation
(St): Collective screen
Y: PVC inner sheath
SWA: Galvanized steel wires
Y: PVC outer sheath
fl:  Reduced flame propagation
LSLH: Low emission of smoke and halogens
 


 TOP
Characteristics
Construction characteristics
Conductor material Bare copper  
Conductor flexibility Stranded class 2  
Insulation PE  
Overall screen Tinned copper drain wire + aluminium/polyester tape  
Inner sheath PVC  
Armour type Galvanized steel wires  
Outer sheath Tight buffer  
Electrical characteristics
Operating voltage 300V  
Mechanical characteristics
Mechanical resistance to impacts Good  
Usage characteristics
Fire retardant IEC 60332-3-22  
Oil resistance ASTM D 1047  
Smoke density Low  
Slightly halogenous yes  
Operating temperature, range -20 .. 60°C  
Max. conductor temperature in service 70°C  
Standard EN  

 TOP
Your selection
Number of pairs  
Conductor cross-section  mm²
Minimum outer diameter  mm
Maximum outer diameter  mm
Approximate weight  kg/km
Sheath colour  
Apply
Reset
Results   29/29
Select all Items Nexans ref. Name nb pairs Cross section (mm²) Min. outer diam. (mm) Max. outer diam. (mm) Approx. weight (kg/km)
10098167 RE-2Y(St)YSWAY - fl LSLH 1x2x0.5 1 0.5 9.5 10.5 212
10201218 RE-2Y(St)YSWAY - fl LSLH 2x2x0.5 2 0.5 10.2 11.2 232
10098169 RE-2Y(St)YSWAY - fl LSLH 4x2x0.5 4 0.5 13.5 14.9 352
10098113 RE-2Y(St)YSWAY - fl LSLH 8x2x0.5 8 0.5 15.9 17.5 470
10098174 RE-2Y(St)YSWAY - fl LSLH 12x2x0.5 12 0.5 18.2 20.1 598
10098175 RE-2Y(St)YSWAY - fl LSLH 16x2x0.5 16 0.5 20.4 22.5 713
10098176 RE-2Y(St)YSWAY - fl LSLH 20x2x0.5 20 0.5 22.5 24.8 953
10098177 RE-2Y(St)YSWAY - fl LSLH 24x2x0.5 24 0.5 23.9 26.3 1062
10098178 RE-2Y(St)YSWAY - fl LSLH 1x2x0.75 1 0.75 10.0 11.1 236
10101849 RE-2Y(St)YSWAY - fl LSLH 1x2x0.75 1 0.75 10.0 11.1 236
10201219 RE-2Y(St)YSWAY - fl LSLH 2x2x0.75 2 0.75 10.1 11.1 236
10201223 RE-2Y(St)YSWAY - fl LSLH 2x2x0.75 2 0.75 10.1 11.1 236
10098180 RE-2Y(St)YSWAY - fl LSLH 4x2x0.75 4 0.75 14.6 16.2 411
10098181 RE-2Y(St)YSWAY - fl LSLH 8x2x0.75 8 0.75 17.6 19.4 573
10098182 RE-2Y(St)YSWAY - fl LSLH 12x2x0.75 12 0.75 20.3 22.4 736
10098183 RE-2Y(St)YSWAY - fl LSLH 16x2x0.75 16 0.75 23.5 25.9 1045
10098184 RE-2Y(St)YSWAY - fl LSLH 20x2x0.75 20 0.75 25.0 27.6 1176
10098185 RE-2Y(St)YSWAY - fl LSLH 24x2x0.75 24 0.75 26.7 29.4 1319
10098186 RE-2Y(St)YSWAY - fl LSLH 1x2x1.34 1 1.34 11.0 12.2 289
10101851 RE-2Y(St)YSWAY - fl LSLH 1x2x1.34 1 1.34 11.0 12.2 289
10201220 RE-2Y(St)YSWAY - fl LSLH 2x2x1.34 2 1.34 11.3 12.5 296
10201244 RE-2Y(St)YSWAY - fl LSLH 2x2x1.34 2 1.34 11.3 12.5 296
10098188 RE-2Y(St)YSWAY - fl LSLH 4x2x1.34 4 1.34 17.2 18.9 546
10101853 RE-2Y(St)YSWAY - fl LSLH 4x2x1.34 4 1.34 17.2 18.9 546
10098189 RE-2Y(St)YSWAY - fl LSLH 8x2x1.34 8 1.34 20.7 22.8 784
10098190 RE-2Y(St)YSWAY - fl LSLH 12x2x1.34 12 1.34 24.7 27.3 1189
10098191 RE-2Y(St)YSWAY - fl LSLH 16x2x1.34 16 1.34 28.1 31.0 1462
10098192 RE-2Y(St)YSWAY - fl LSLH 20x2x1.34 20 1.34 30.1 33.2 1667
10098193 RE-2Y(St)YSWAY - fl LSLH 24x2x1.34 24 1.34 32.6 36.0 1938
Add to favorites

 TOP
Electrical characteristics at 20°C


 TOP
Selling delivery information

Minimum bending radius:

10 x outer diameter
To be doubled during laying operations

2 pair cables are assembled as a quad (black and white cores both printed with pair number)


Nexans © copyright 2001 - 2012   Legal Notice | Contact Us | Site Map