The cable has to be oil resistant. Test according to EN60811-2-1 (based on to IEC60811-2-1)
2 times 4 hours at 70°C in oil IRM 902
After 4 hours the cable shall be checked for damage to the isolation. If still ok the test will continue 4 hours more with a final examination of the isolation.
Max tensile strength variation: +/- 40% (HD22.1, table 2, ref no 1.4.2)
Elongation: +/- 40% (HD22.1, table 2, ref no 1.4.3)
|