ALSECURE® FB RHEYHALON® N2XH-O/J E90

Send link to this page print Your Nexans contact on this page
ALSECURE® FB RHEYHALON® N2XH-O/J E90

Power Cable

Circuit Integrity 90 Minutes acc. to DIN 4102-12

Insulation Integrity FE180 acc. to DIN VDE 0472-814

halogenfree with improved behaviour in case of fire acc. to DIN VDE 0266

Description


 Application

ALSECURE RHEYHALON Security cables N2XH-O/J with 90 minutes circuit integrity should be used for DIN installations for security equipments in public buildings, e.g. meeting areas, schools etc. (DIN VDE 0108) as well as in hospitals (DIN VDE 0107) or other safety relevants areas where a circuit integrity acc. to DIN 4102-12 over 90 minutes for power distribution is required.

This cable is suitable for interior installations on, in and under plaster, in dry, wet and damp rooms as well as in masonry and in concrete. A direct installation in ground and water is not allowed. An installation in open air areas requires a protection from sun light (UV-radiation). Under usage of tubes an outdoor or ground installation is possible, if the cable is guarded against water and moisture.

This cable conforms to the circuit integrity requirements of E90 in accordance with DIN 4102-12 and of the requiremants of the 'Brandschutztechnischen Richtlinien' (supplement 1 to DIN VDE 0108). The circuit integrity is guaranteed by an operating voltage of 400 V.

 Standards

 circuit integrity E90             DIN VDE 4102-12

 insulation integrity FE180  IEC 60331 and VDE 0472-814

 halogen free                          IEC 60754-2 and EN 50267-2-1

 corrosive gases                   IEC 60754-2 and EN 50267-2-2

 flame retardant                     IEC 60332-3 and EN 50266-2-4 und -2-5

 smoke density                      IEC 61034-2 and EN 50268-2

 fire retardant                          IEC 60332-1-2 and VDE 0482-265-2-1

 

*depending on the method of installation regarding to ABP (general construction inspection test certificate)


 TOP
Characteristics
Construction characteristics
Halogen free IEC 60754  
Sheath colour Orange  
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV  
Test voltage 4kV  
Usage characteristics
Smoke density EN 50268  
Fire retardant IEC 60332-1  
Operating temperature, range -30 .. 90°C  
Maximum operating temperature 90°C  
Bending factor when laying 12(xD)  

 TOP
Your selection
Outer Diameter  mm
Approximate weight  kg/km
Conductor cross-section  mm²
Number of cores  
Apply
Reset
Results   70/70
Select all Items Nexans ref. Outer Diameter (mm) Approx. weight (kg/km) Cross section (mm²) Nb. of cores
Make to order product 79161001 22 530 1.5 10
Make to order product 79161002 24 610 2.5 10
Make to order product 79161201 23 580 1.5 12
Make to order product 79161202 25 690 2.5 12
Make to order product 79162401 30 960 1.5 24
10087920 18 590 10 3
10140227 15 330 4 3
10087919 16 420 6 3
79163001 13 260 1.5 3
Make to order product 79163120 43 5010 120 3
Make to order product 79163150 47 6080 150 3
79163016 20 790 16 3
Make to order product 79163185 51 7520 185 3
Make to order product 79163240 58 9750 240 3
Make to order product 79163025 25 1200 25 3
Make to order product 79163035 27 1650 35 3
Make to order product 79163050 30 2220 50 3
Make to order product 79163070 34 3000 70 3
Make to order product 79163095 40 3950 95 3
10008706 14 290 1.5 4
10136460 19.5 730 10 4
10136423 21.5 990 16 4
10008705 15 330 2.5 4
10070788 26 1500 25 4
10050911 16 410 4 4
10126530 18 520 6 4
Make to order product 79164120 47 6270 120 4
Make to order product 79164150 52 7890 150 4
Make to order product 79164185 55 9710 185 4
Make to order product 79164240 61 12340 240 4
Make to order product 79164035 30 2100 35 4
Make to order product 79164050 34.5 2600 50 4
Make to order product 79164070 37 3700 70 4
Make to order product 79164095 41 4900 95 4
10034215 16 350 1.5 5
10041904 21 920 10 5
10015157 18 400 2.5 5
10044592 18.5 490 4 5
10024464 19 620 6 5
79165016 24 1300 16 5
79165025 29 1860 25 5
79165035 32 2560 35 5
79167001 17 380 1.5 7
79167002 19 460 2.5 7
Make to order product 79167004 4 7
Make to order product 7916.... 22 980 25 2
Make to order product 7916.... 26 1240 35 2
Make to order product 7916.... 29 1710 50 2
Make to order product 7916.... 32.5 2130 70 2
Make to order product 7916.... 36 3010 95 2
Make to order product 7916.... 40 3680 120 2
10061399 14 290 2.5 3
79161120 21 1340 120 1
79161150 23 1650 150 1
Make to order product 79161016 11.5 250 16 1
10041821 25.5 2010 185 1
79161240 28 2570 240 1
Make to order product 79161025 13 360 25 1
79161300 30.5 3160 300 1
Make to order product 79161035 14 480 35 1
Make to order product 79161400 34 4030 400 1
Make to order product 79161050 15.5 600 50 1
Make to order product 79161070 17.5 830 70 1
79161095 19.5 1100 95 1
Make to order product 79162001 12.5 210 1.5 2
Make to order product 79162010 16.5 510 10 2
Make to order product 79162016 18.5 670 16 2
Make to order product 79162002 13.5 250 2.5 2
Make to order product 79162004 14.5 290 4 2
Make to order product 79162006 15.5 360 6 2
Add to favorites

 TOP
ALSECURE® FB RHEYHALON® N2XH-O/J E90   Normen met betrekking tot brandveiligheid van elektrotechnische installaties (37 kB)