ALSECURE® FB RHEYHALON® N2XCH E90

Send link to this page print Your Nexans contact on this page
ALSECURE® FB RHEYHALON® N2XCH E90

Power Cable

Circuit Integrity 90 Minutes acc. to DIN 4102-12

Insulation Integrity FE180 acc. to DIN VDE 0472-814

halogen free with improved behaviour in case of fire acc. to DIN VDE 0266

Description

 

 

RHEYHALON Security cables N2XCH with 90 minutes circuit integrity should be used for DIN installations for security equipments in public buildings, e.g. meeting areas, schools etc. (DIN VDE 0108) as well as in hospitals (DIN VDE 0107) or other safety relevants areas where a circuit integrity acc. to DIN 4102-12 90 minutes for power distribution is required.

This cable is suitable for interior installations on, in and under plaster, in dry, wet and damp rooms as well as in masonry and in concrete. A direct installation in ground and water is not allowed. An installation in open air areas requires a protection from sun light (UV-radiation). Under usage of tubes an outdoor or ground installation is possible, if the cable is guarded against water and moisture.

This cable conforms to the circuit integrity requirements of E90* in accordance with DIN 4102-12 and of the requiremants of the 'Brandschutztechnischen Richtlinien' (supplement 1 to DIN VDE 0108). The circuit integrity is guaranteed by an operating voltage of 400 V.

 

 

Standards

 circuit integrity E90                 DIN VDE 4102-12

 insulation integrity FE180      IEC 60331 und VDE 0472-814

 halogen free                              IEC 60754-2 und EN 50267-2-1

 corrosive gases                       IEC 60754-2 und EN 50267-2-2

 flame retardant                        IEC 60332-3 und EN 50266-2-4 und -2-5

 smoke density                         IEC 61034-2 und EN 50268-2

 fire retardant                            IEC 60332-1-2 und VDE 0482-265-2-1

 

 

*depending on the method of installation regarding to ABP (general construction inspection test certificate)


 TOP
Characteristics
Construction characteristics
Halogen free IEC 60754-2  
Sheath colour Orange  
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV  
Test voltage 4kV  
Usage characteristics
Smoke density EN 50268-2  
Operating temperature, range -30 .. 90°C  
Maximum operating temperature 90°C  
Fire retardant IEC 60332-1  
Bending factor when laying 12(xD)  

 TOP
Your selection
Number of cores  
Conductor cross-section  mm²
Outer Diameter  mm
Approximate weight  kg/km
Fire load  kWh/m
Apply
Reset
Results   34/34
Select all Items Nexans ref. Nb. of cores Cross section (mm²) Outer Diameter (mm) Approx. weight (kg/km) Fire load (kWh/m)
Make to order product 10192061 3 2.5 15 280 0.75
10034216 4 2.5 17 330 1
10049774 4 4 18 440 1.1
10025511 4 6 19 570 1.3
10069828 4 16 25 1200 1.9
10024465 4 25 29 1700 2.7
10015022 4 35 32 2200 3.1
10028814 4 50 35 2800 3.7
10073024 4 70 40 3900 4.7
10071309 4 95 44 5200 5.6
10137604 4 120 50 6600 6.8
10065894 4 185 61 10400 10.5
79165121 12 1.5 21 520 1.7
79165122 12 2.5 23 700 2.2
10065292 3 1.5 14 230 0.65
Make to order product 79165... 3 10 20 700 1.25
Make to order product 79165... 3 120 47 5500 5.8
Make to order product 79165... 3 150 52 6700 7.3
Make to order product 79165... 3 16 22 980 1.4
Make to order product 79165... 3 185 56 8300 9
Make to order product 79165... 3 240 62 10000 10.5
Make to order product 79165... 3 25 27 1430 2.3
Make to order product 79165... 3 35 30 1800 2.8
Make to order product 79165... 3 4 17 270 0.85
Make to order product 79165... 3 50 32 2400 3.2
Make to order product 79165... 3 6 18 480 1
Make to order product 79165... 3 70 37 3350 4
Make to order product 79165... 3 95 41 4350 4.7
79165401 4 1.5 16 280 0.9
79165410 4 10 23 850 1.6
79165415 4 150 56 8000 8.4
79165424 4 240 68 13000 12.5
79165701 7 1.5 19 420 1.4
79165702 7 2.5 20 500 1.5
Add to favorites

 TOP
ALSECURE® FB RHEYHALON® N2XCH E90   Normen met betrekking tot brandveiligheid van elektrotechnische installaties (37 kB)

See all approval certificates Security Cables new
N2XH / N2XCH E90 approval certificate (in German only)   N2XH / N2XN2XH / N2XCH E90 approval certificate (in German only)
N2XH / N2XCH E30-E90 PUK approval certificate (in German only)   N2XH / N2XCH E30-EN2XH / N2XCH E30-E90 PUK approval certificate (in German only)